How To Change Blower Speed On Lennox Furnace
Please register to participate in our discussions with 2 million other members - it'south costless and quick! Some forums can only exist seen by registered members. Subsequently yous create your account, you'll be able to customize options and access all our 15,000 new posts/day with fewer ads.
12-10-2010, 03:twenty PM |
Hi folks, I have a dilemma here and wonder any experts out here tin shed some lights. I have a 2003 Lennox Furnace (model 48C-115-3), information technology's a four ton unit that sizes roughly 2100 sq.ft. unmarried zone. I have a 2 story home with a basement. The furnace is located in the basement (finished) and seems to heat the house fairly well. I noticed the fan speed board had the cool set to loftier (black wire) (this is normal every bit I know cooling needs to have fan speed set to high). However, on the board where information technology said "oestrus" it has the fan speed low (red) plugged into information technology. My furnace fan has 4 speed (goes from blackness, chocolate-brown, yellow, cerise) black being highest speed and carmine being everyman.) I take always read the fan speed should be on depression for heating and high for cooling. However, I open the Lennox manual and noticed it had a chart diagram for fan speed and read....for my unit of measurement model (48C-115-3) showed black wire (Loftier) for cooling and brown wire (med-high) for heating. Now, the unit currently has Blood-red (depression) plugged onto heating... which shows the lowest speed. Should I get out information technology solitary or switch it to manufactory recommendation at med-high? I heard ane matter but read some other. Basically I want to discover out if I could possibly damage anything past changing it to med-high. I too don't want the pressure to be too loftier since manufactory recommended med-high when it is currently set up at low. Please help. cheers, |
12-11-2010, 08:04 PM | |||
| |||
change it to med-high setting.. You abode volition warm faster too thus cut downwards on the run time of the gas fired furnace.. |
12-12-2010, 05:50 AM | |||
| |||
You tin can telephone call Lennox and ask them - they have the respond. |
12-12-2010, 07:fifty AM | |||
| |||
Every hoise is different... The installer should have done some calculations and measurements to see how quickly the temperature rises in the rooms furthest from the furnace and how that compares to the rates of heating in the heat exchanger of the furnace. Ideally the fan should never be sent so loftier as to blow cold air to the furthest rooms. Thus the low speed is often the almost comfortable. For cooling things are different -- moving the air makes your skin feel cooler all by itself. So long equally the fan speed is not so high that the A/C evaporator is not covered in ice and no moisture is being removed you want that air pushed out fast. I dubiousness you lot'll damage anything past switching the oestrus speed jumper, but I suspect faster speeds are going to make your family members (especially older females) complain that it shifts between too absurd and too warm , which is generally why the lowest speed is preferred even if it means the overal run time is a fleck longer. I dubiousness you'd run into much difference in the energy bill, it is comfort cistron... |
12-fifteen-2010, 05:sixteen PM | |||
| |||
If you lot accept no issues with the heat why does information technology need to be changed ? To have a slower fan speed for heat is normal. |
12-22-2010, 02:37 PM | |||
| |||
have an hvac tech figure it out. If the fan speed is too low it could crusade the temperature ascent across the furnace to not exist in spec and cause your heat exchanger to crack or keep tripping your high limit switch. Ideally, y'all want your fan speed on medium low or medium howdy. Not Low or High. My fan speed for heating in on medium high and it falls right smack in the middle of my furnace temerpature rise of 40-seventy degrees. (supply air minus the temperature of the return air) |
12-22-2010, 02:38 PM | |||
| |||
Quote: Originally Posted past beach.guy If y'all take no issues with the rut why does it need to be inverse ? To have a slower fan speed for heat is normal. Only it can't exist besides low |
12-22-2010, 02:40 PM | |||
| |||
Quote: Originally Posted past frankgn87 alter information technology to med-loftier setting.. You home volition warm faster besides thus cutting down on the run time of the gas fired furnace.. Not true. The faster the air is blowing, the more information technology cools down the heat exchanger, lowering temps at the supply registers. |
12-23-2010, 08:34 PM |
Quote: Originally Posted by Cattknap You can call Lennox and enquire them - they take the reply. I called them, and took about 45 minutes for someone to respond and then shift me to some other department for another forty minutes of wait time. When someone really was able to talk to me, his reply was "we do not talk to the abode owners." what a bunch of ..."fill in the blank" |
12-23-2010, 08:40 PM |
Well, I understand all the facts of fan speed besides loftier = colder air blown into the supply registers. As well low = warmer air but oestrus exchanger problem. I actually took the fourth dimension in the concluding 2 days to measure the difference in oestrus rise (supply minus return) and when information technology is set at med-low , the rut rising is 55 degrees (131 supply and 72 return) (house kept at 73/74. When information technology is set at the lowest speed (it's threescore) my furnace temerpature rise is recommended at forty-70 degrees. Then at 55 or sixty is both expert. |
Detailed information nearly all U.South. cities, counties, and cipher codes on our site: City-data.com.
All times are GMT -six.
Source: http://www.city-data.com/forum/house/1148331-fan-speed-lennox-furnace.html
Posted by: hoggardtwerfell.blogspot.com
0 Response to "How To Change Blower Speed On Lennox Furnace"
Post a Comment